Back to COSI-CT F3 product page Current Transformers specifications
- Single phase, three phase, and six phase system configurations available
- Sensor enclosure; fiberglass box;
- Type A and Type B:
Dimensions: 14 x 12 x 5.74 inches
Weight: 20 lbs
IP66 - Closed Loop F3:
Dimensions: 16 x 14 x 5.74 inches
Weight: 45 lbs
IP66
- Type A and Type B:
- 20-meter length wrap-around sensing fiber standard, other lengths available on request
- Programmable output scaling
- Output format options: analog voltage (IEC 60044-8 200 mV and 4V formats), current (1 A or 5 A metering format), digital (IEC 61850)
| COSI-CT F3 | Type A | Type B | Closed Loop |
|---|---|---|---|
| Class .1 | x | ||
| Class .15s | x | x | |
| Class .2s | x | x | |
| Class .3 | x | x | |
| Class 1 | x | ||
| Class 5 | x | ||
| AC | x (up to 20 kHz) |
x (10 Hz to 3 kHz) |
x (up to 20 kHz) |
| DC | x | x | |
| AC/DC | x | x | |
| Sensor box HV isolated | x | ||
| Max distance between electronics and sensor |
1 km | 10 km (no repeater) |
100 m |
| Fiber cable required | x | x | x |
| Copper cables required | x | x |
Applications
| COSI-CT F3 | Type A | Type B | Closed Loop |
|---|---|---|---|
| Bushing | x | x | x |
| Currents > 160 kA | x | ||
| GIS | x | x | |
| Calibration | x | ||
| Field service | x | x | x |
| Metering | x | x | |
| Protection | x | x | x |
| Cable monitoring | x | x |
Rated current range vs. number of fiber wraps
| # of fiber wraps | Minimum rated current* | Max rated current* |
|---|---|---|
| 1 | 2000 A | 80 kA |
| 2 | 1000 A | 40 kA |
| 5 | 400 A | 16 kA |
| 10 | 200 A | 8 kA |
| 20 | 100 A | 4 kA |